The traditional approach to shielding design for diagnostic x-ray faci
lities has been to designate as primary barriers the floor and those w
alls on which the useful beam may impinge, and to ignore the attentuat
ion provided by the patient, grid, cassette, cassette holder, and x-ra
y table in computing the required thickness of these barriers. The deg
ree of attenuation provided by the aforementioned materials has been m
easured on three-phrase x-ray equipment including a variety of modern
x-ray tables, grids, and cassettes. The primary beam is shown to be at
tenuated by more than two orders of magnitude at 100 kVp by the x-ray
tables tested prior to impinging on the floor (ignoring patient attent
uation). If patient attenuation is included, the attenuation is more t
han three orders of magnitude. Transmission factors as well as lead an
d concrete equivalencies for the various attenuation materials have be
en determined and included in tabular form. Example calculations for a
heavy work load show that only a modest amount of concrete is require
d in the floor as a primary barrier if attenuation by these materials
is taken into consideration (less than 2.5 cm at 80 kVp and less than
4 cm at 100 kVp) and the required secondary barrier may be thicker tha
n the primary barrier. As verification, the actual exposure just below
the table bucky was measured over a period of 3 weeks in tow radiogra
phic rooms using film dosimetry, and was found to be less than 0.015 m
Sv week(-1) (1.5 mR/week) for a heavy work load of 24 patients per day
, thus no primary beam shielding would have been required in the floor
for these x-ray rooms.