Maa. Wahab et K. Matsuura, MODIFIED FOURIER-TRANSFORM LIGHTNING SURGE ANALYSIS OF AN OVERHEAD LINE-UNDERGROUND COAXIAL (CV) CABLE SYSTEM .2. SYSTEM LIGHTNING SURGE RESPONSE, Electric power systems research, 31(1), 1994, pp. 43-49
The lightning surge analysis of an overhead line-underground CV cable
transmission system has been carried out using the modified Fourier tr
ansform with a multiconductor representation. The frequency dependence
of the transmission system components such as the overhead transmissi
on line, underground cable and towers has been analyzed. A digital sim
ulation based on this analysis has been developed and applied to a 77
kV three-phase single-circuit system. The results for a direct hit by
a lightning stroke at the riser pole tower top show that the overvolta
ges at the riser pole increase with increase in the tower footing resi
stance and that the phase conductor overvoltages are greatly affected
by the CV cable. The cable open-tie overvoltages decrease with increas
e in the cable length.