JOINT TREATMENT OF INDUSTRIAL EFFLUENT - CASE-STUDY OF LIMASSOL INDUSTRIAL ESTATE

Citation
I. Hadjivassilis et al., JOINT TREATMENT OF INDUSTRIAL EFFLUENT - CASE-STUDY OF LIMASSOL INDUSTRIAL ESTATE, Water science and technology, 29(9), 1994, pp. 99-104
Citations number
4
Categorie Soggetti
Water Resources","Environmental Sciences","Engineering, Civil
ISSN journal
02731223
Volume
29
Issue
9
Year of publication
1994
Pages
99 - 104
Database
ISI
SICI code
0273-1223(1994)29:9<99:JTOIE->2.0.ZU;2-M
Abstract
The treatment plant has been designed and installed for the treatment of wastewater discharged from various industries at Limassol industria l Estate. The total daily flow and biological load after the last exte nsion of the plant are 1000-1200m(3)/d and 220-264kg BOD5/d respective ly. Chemical treatment followed by biological treatment is applied. Th e main steps of the treatment process are as follows: equalization, fl otation, coagulation-flocculation, settlement of chemical sludge, pH-a djustment, nutrient addition, aeration of activated sludge, settlement of biological sludge, chlorination and sludge stabilization. The effi ciency of the plant with respect to BOD5 and COD removal is over 90%. The quality of the treated effluent is BOD5 < 15mg/l and COD < 40mg/l. The concentration of trace elements are below the recommended limits for reclaimed water used for irrigation purposes.