MEASUREMENT OF VENTILATION AND AEROSOL-PARTICLES IN BUILDINGS

Citation
Sb. Riffat et Kw. Cheong, MEASUREMENT OF VENTILATION AND AEROSOL-PARTICLES IN BUILDINGS, International journal of energy research, 17(1), 1993, pp. 45-55
Citations number
NO
Categorie Soggetti
Energy & Fuels",Engineering,"Nuclear Sciences & Tecnology
ISSN journal
0363907X
Volume
17
Issue
1
Year of publication
1993
Pages
45 - 55
Database
ISI
SICI code
0363-907X(1993)17:1<45:MOVAAI>2.0.ZU;2-S
Abstract
The work described in the paper is concerned with the measurement of t he flow of tracer gas and aerosol particles in rooms. Measurements wer e carried out in single- and two-zone systems using SF, tracer gas and oil-smoke particles. Initial tests were carried out in a single-zone system using different arrangements of window opening. Results indicat ed that tracer-gas exchange rates were generally higher than particle exchange rates. This was due to the fact that the ventilation air ente ring the zone contained a significant concentration of particles but a negligible quantity of tracer gas. The exchange rates of tracer gas a nd smoke particles through a doorway were also measured in a two-zone system. The doorway coefficients of discharge were calculated using a theory based on the Bernoulli equation. The coefficients of discharge for the opening were in the range 0.4-0.96 for tracer gas measurements and 0.15-0.42 for smoke-particle measurements.