Nj. Hewitt et al., THE CHOICE OF A THERMOSTATIC EXPANSION VALVE FOR A CFC12 REFRIGERATION SYSTEM RETROFITTED WITH HFC134A, International journal of energy research, 17(3), 1993, pp. 153-164
Citations number
NO
Categorie Soggetti
Energy & Fuels",Engineering,"Nuclear Sciences & Tecnology
There is a need to develop a suitably charged thermostatic expansion v
alve to work with systems charged with HFC134a. The conventional CFC12
cross-charged valve does work, but with a slight loss of superheat se
nsitivity. A pure HFC134a charged valve lacks a constant superheat ove
r a range of evaporator temperatures, and may require a smaller orific
e size than the conventional cross-charged valve.