THE COOLING OF A HEAT-GENERATING BOARD INSIDE A PARALLEL-PLATE CHANNEL

Citation
A. Bejan et al., THE COOLING OF A HEAT-GENERATING BOARD INSIDE A PARALLEL-PLATE CHANNEL, International journal of heat and fluid flow, 14(2), 1993, pp. 170-176
Citations number
9
Categorie Soggetti
Mechanics,"Engineering, Mechanical
ISSN journal
0142727X
Volume
14
Issue
2
Year of publication
1993
Pages
170 - 176
Database
ISI
SICI code
0142-727X(1993)14:2<170:TCOAHB>2.0.ZU;2-P
Abstract
This paper addresses the fundamental question of how to position a hea t-generating board inside a parallel-plate channel, where it is cooled by forced convection. It is shown that when the board substrate is a relatively good thermal conductor, the best board position is near one of the channel walls, and the worst position is in the middle of the channel. The best and worst positions switch places when the board sub strate is a relatively poor conductor. The optimal spacing between a h eat-generating surface (uniform temperature, or uniform heat flux) and the insulated wall that completes a parallel-plate channel is reporte d. Finally, it is shown under what conditions it is advantageous to di vide a heat-generating board into two or more equidistant boards insid e the same channel, when the total rate of heat generation of all the boards and the channel spacing are fixed.