O. Comakli et al., Determination of optimum working conditions in heat-pumps using nonazeotropic refrigerant mixtures, ENERG CONV, 40(2), 1999, pp. 193-203
The objective of this work is to investigate experimentally the effects of
mixture concentrations, source temperature, flow rate of condenser cooling
water and air flow rate in the cooling tower on the Coefficient of performa
nce (COP) and eta(ex) (exergetic efficiency) values of vapour compression h
eat pump systems. The experimental apparatuses consist of a vapour compress
ion heat pump conducting according to the liquid to air principle, refriger
ant mixture unit, cooling tower, measuring elements and other auxiliary equ
ipment. Refrigerants R11, R12, R22 and six of their binary mixtures which c
ontain about 25%, 50% and 75% mass fractions of R22 were tested. The experi
ments were performed in the region of source temperatures from Is to 28 deg
rees C and flow rates of condenser cooling water from 500 to 1250 kg/h. Fou
r different air flow rates were chosen in those experiments in the cooling
tower. To determine the efficiency of the chosen parameters on the system a
nd optimum working conditions, an experimental design method suggested by G
enichi Taguchi was used. In this study, it was observed that the COP and et
a(ex) increased with the addition of R22 to the system over R11 and R12 pur
e refrigerants. (C) 1998 Elsevier Science Ltd. All rights reserved.