Electromagnetic interference from a three phase double circuit 765-kV testline

Citation
Jb. Kim et al., Electromagnetic interference from a three phase double circuit 765-kV testline, IEEE POW D, 14(1), 1999, pp. 266-271
Citations number
7
Categorie Soggetti
Eletrical & Eletronics Engineeing
Journal title
IEEE TRANSACTIONS ON POWER DELIVERY
ISSN journal
08858977 → ACNP
Volume
14
Issue
1
Year of publication
1999
Pages
266 - 271
Database
ISI
SICI code
0885-8977(199901)14:1<266:EIFATP>2.0.ZU;2-9
Abstract
This paper presents the results of long-term electromagnetic interference(E MI) measurements on the bundle of 6 Cardinal conductors tested at the Kocha ng 765-kV full scale test line. The instrumentation, and the most important features of the facilities are also described. This new 3-phase double cir cuit test line can be energized at line-to-line voltages up to 850 kV. The analysis of the data shows that the 6-Cardinal conductor bundle meets the r adio and television interference guidelines of the Korea Electric Power Cor poration (KEPCO).