To demonstrate the possibility of manufacturing a HTS power transmission ca
ble with low AC losses, we fabricated a 10 m long cable conductor and a cry
osystem. The conductor was wound in a four-layer design out of 2 km Ag/Bi-2
223 tapes. We determined a critical current of 5000 A. Loss measurements we
re performed with an electric method which detects the voltage drop along t
he conductor with a lock-in technique and a calorimetric method which measu
res the temperature rise along the conductor. Both methods yield the same l
ow loss values of only 0.8 W/m at 77 K and 2000 A(rms)/50 Hz. This is due t
o the low loss winding scheme we used which assures an equal current distri
bution in all four layers through transformatoric coupling. We applied the
uniform current distribution model and added the nonlinear V-l curve to des
cribe quantitatively the obtained results. (C) 1998 Elsevier Science B.V. A
ll rights reserved.