The determination of FFA concentration in transformer oil by fluorescence measurements

Citation
R. Blue et al., The determination of FFA concentration in transformer oil by fluorescence measurements, IEEE DIELEC, 5(6), 1998, pp. 892-895
Citations number
6
Categorie Soggetti
Eletrical & Eletronics Engineeing
Journal title
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION
ISSN journal
10709878 → ACNP
Volume
5
Issue
6
Year of publication
1998
Pages
892 - 895
Database
ISI
SICI code
1070-9878(199812)5:6<892:TDOFCI>2.0.ZU;2-9
Abstract
Condition monitoring of the paper winding of power transformers involves th e measurement of the concentration of 2-furaldehyde, also called furfuralde hyde (FFA) in the transformer oil, Measuring the concentration of FFA in th e ail gives a reliable indication of the condition of the paper insulation. This measurement has routinely been performed by using techniques such as high performance liquid chromatography. We report for the first time the us e of fluorescence-based methods for the assessment of FFA in transformer oi l.