Condition monitoring of the paper winding of power transformers involves th
e measurement of the concentration of 2-furaldehyde, also called furfuralde
hyde (FFA) in the transformer oil, Measuring the concentration of FFA in th
e ail gives a reliable indication of the condition of the paper insulation.
This measurement has routinely been performed by using techniques such as
high performance liquid chromatography. We report for the first time the us
e of fluorescence-based methods for the assessment of FFA in transformer oi
l.