Heat transfer and pressure drop during condensation of refrigerant 134a inan axially grooved tube

Citation
D. Graham et al., Heat transfer and pressure drop during condensation of refrigerant 134a inan axially grooved tube, INT J HEAT, 42(11), 1999, pp. 1935-1944
Citations number
20
Categorie Soggetti
Mechanical Engineering
Journal title
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER
ISSN journal
00179310 → ACNP
Volume
42
Issue
11
Year of publication
1999
Pages
1935 - 1944
Database
ISI
SICI code
0017-9310(199906)42:11<1935:HTAPDD>2.0.ZU;2-B
Abstract
Condensation experiments have been performed over a mass flux range of 75-4 50 kg m(-2) s(-1) in an 8.91 mm inside diameter, axially grooved, micro-fin tube with R134a. At 75 kg m(-2) s(-1), the axially grooved tube performs m arginally better than a smooth tube, but worse than a similarly grooved tub e with an 18 degrees helix angle. Mass fluxes at 150 kg m(-2) s(-1) and gre ater show broad quality ranges in which the axially grooved tube performs s ignificantly better than both smooth and helically grooved tubes. Pressure drop characteristics of the axially grooved tube are similar to those found in an 18 degrees helix angle tube. (C) 1998 Elsevier Science Ltd. All righ ts reserved.