In this paper, a technique is presented for measuring the harmonic imp
edances of an unbalanced three-phase distribution feeder. The techniqu
e uses transients in bus voltages and feeder currents generated by sev
eral close-trip operations of the shunt capacitor bank. The work is ba
sed on the assumption that the impedance of feeder does not change ove
r time during which the switching operations are performed. Mathematic
al development of the technique is verified with the laboratory and th
e field tests. The technique provided good measurements of the harmoni
c impedances up to 1.5 kHz for the given capacitor sizes. Statistical
indices were developed to assess the accuracy of the estimated impedan
ce values.