R. Kumar et al., AUGMENTATION OF OUTSIDE TUBE HEAT-TRANSFER COEFFICIENT DURING CONDENSATION OF STEAM OVER HORIZONTAL COPPER TUBES, International communications in heat and mass transfer, 25(1), 1998, pp. 81-91
An experimental investigation has been carried out to find the condens
ing side heat transfer coefficient, h(0), during condensation of steam
over a plain tube, a circular integral-fin tube(CIFT) and a spine int
egral-fin tube(SIFT). The GIFT and SIFT have enhanced the h(0) by a fa
ctor of 2.5 and 3.2 respectively. The experimental values of h(0) for
GIFT were compared with those predicted from different models. The Hon
da and Nozu model underpredicted the values of h(0) in a range of 10 t
o 20 percent. (C) 1998 Elsevier Science Ltd.