Ay. Wu et Yx. Yin, FAULT-CURRENT LIMITER APPLICATIONS IN MEDIUM-VOLTAGE AND HIGH-VOLTAGEPOWER DISTRIBUTION-SYSTEMS, IEEE transactions on industry applications, 34(1), 1998, pp. 236-242
Electronically triggered fault-current limiters have been used in medi
um-and high-voltage power distribution systems to limit the available
short-circuit current tu a lower level, so that the underrated switchg
ear can be operated safely, However, to insure a safe and proper usage
of these devices, the following major operating parameters need to be
considered: 1) selection of trigger level; 2) selection of di/dt; 3)
effect of the capacitor bank and stray capacitances; and 4) coordinati
on between these devices and phase overcurrent (o/c) relays at the fau
lted breaker, This paper will examine these major operating parameters
, evaluate the performance of the current limiters tinder various simu
lated fault conditions, and develop application guidelines fur current
limiters.