Am. Zahedi et al., OPTIMUM LOCATION AND SIZE OF THE LC HARMONIC FILTERS IN THE FEEDERS WITH UNIFORMLY DISTRIBUTED LINEAR AND NONLINEAR LOADS, Electric power systems research, 44(2), 1998, pp. 127-136
This paper analyzes the harmonic voltages and currents in a distributi
on feeder with uniformly distributed linear and nonlinear loads. Two m
ajor topics are addressed: 1. The determination of the maximum tolerab
le nonlinear load apparent power in the feeder, with and without shunt
capacitance, that can produce 5% total harmonic distortion of the vol
tage (VTHD); 2. The second subject deals with shunt LC filter optimiza
tion. The goal is to determine the best tuning frequency and location
of the filter which minimizes the maximum VTHD in the feeder. Also, th
e effect of the triple harmonics trapping transformer, grounded-wye/de
lta transformer (GWDT), is discussed. The installation of the LC filte
r and GWDT at the capacitor bank location, at 2/3 of the feeder length
, which minimizes the 60 Hz power loss, is considered. To make the res
ults of this study more useful, it is attempted to provide basic guide
lines for the best location and the size of the LC filter and GWDT for
any distribution feeder. (C) 1998 Elsevier Science S.A.