ANALYSIS OF CORONA LOSSES ON MONOPOLAR DC TRANSMISSION-LINES

Citation
M. Abdelsalam et A. Mufti, ANALYSIS OF CORONA LOSSES ON MONOPOLAR DC TRANSMISSION-LINES, Electric power systems research, 44(2), 1998, pp. 145-154
Citations number
19
Categorie Soggetti
Engineering, Eletrical & Electronic
ISSN journal
03787796
Volume
44
Issue
2
Year of publication
1998
Pages
145 - 154
Database
ISI
SICI code
0378-7796(1998)44:2<145:AOCLOM>2.0.ZU;2-R
Abstract
This paper presents a charge-simulation-based method to solve the equa tions describing the ionized field around monopolar transmission lines . The method is applied for calculating the corona power-loss and grou nd-level current-density profile of the conductor bundles of two and t hree subconductors. Different orientations of the conductor bundle is sought to investigate how the ground-level current-density profile is influenced by the orientation of the bundle with respect to the ground plane. The change of the corona onset voltage from point-to-point on each subconductor is taken into account. The calculated corona power-l oss and ground-level current-density of bundle conductors agreed fairl y with those measured experimentally for a laboratory model. (C) 1998 Elsevier Science S.A.