NUMERICAL MODELING OF LIGHTING HVAC INTERACTION IN ENCLOSURES - PART II - EFFECT OF INCLUDING A FLUORESCENT LAMP POSITIVE-COLUMN MODEL/

Citation
Tm. Chung et Dl. Loveday, NUMERICAL MODELING OF LIGHTING HVAC INTERACTION IN ENCLOSURES - PART II - EFFECT OF INCLUDING A FLUORESCENT LAMP POSITIVE-COLUMN MODEL/, HVAC&R research, 4(1), 1998, pp. 85-104
Citations number
31
Categorie Soggetti
Construcion & Building Technology","Engineering, Mechanical",Thermodynamics
Journal title
ISSN journal
10789669
Volume
4
Issue
1
Year of publication
1998
Pages
85 - 104
Database
ISI
SICI code
1078-9669(1998)4:1<85:NMOLHI>2.0.ZU;2-O
Abstract
A numerical model of the fluorescent lamp positive column suitable for use in simulating the interaction between lighting and HVAC systems i n enclosures is presented. The model was modified from existing models in the literature to include only sufficient details for simulating t he conversion of electric energy into light and heat. Details of the f luorescent lamp positive column model are described. The model present ed was incorporated within an existing model, LITEAC1 (described in Pa rt I), that had been used for modelling the interaction between lighti ng and HVAC systems in enclosures. The resulting model, called LITEAC2 , was tested by simulating the performance of a fluorescent lamp in a laboratoy constructed test cell. It was found that the positive column model enabled better predictions for the lighting/air-conditioning in teraction, and improved the modelling of illuminance on room surfaces.