N. Kattan et al., FLOW BOILING IN HORIZONTAL TUBES - PART 2 - NEW HEAT-TRANSFER DATA FOR 5 REFRIGERANTS, Journal of heat transfer, 120(1), 1998, pp. 148-155
A summary of a comprehensive experimental study on flow boiling heat t
ransfer is presented for five refrigerants (R134a, R123, R402A, R404A,
and R502) evaporating inside plain, horizontal, copper tube test sect
ions. The test data were obtained for both 12.00 mm and 10.92 mm diame
ters using hot water as the heating source. Besides confirming known t
rends in flow boiling heat transfer data as a function of test variabl
es, it was also proven that the hear flux level at the dryout point at
the top of the tube in annular flow has a very significant downstream
effect on heat transfer coefficients in the annular flow regime with
partial dryout.