P. Bettini et A. Delorenzi, 400-KV NETWORK HARMONIC IMPEDANCE EVALUATION FROM HARMONIC DISTORTIONMEASUREMENTS AT THE RFX SITE, EUROPEAN TRANSACTIONS ON ELECTRICAL POWER, 8(1), 1998, pp. 31-38
The lack of knowledge of the harmonic frequency behaviour of the extra
-high-voltage (EHV) transmission network prevents the possibility to c
hoose, at the design stage, an appropriate system for harmonic mitigat
ion for current harmonic source loads directly fed by the transmission
network, as well as arc furnaces and facilities for thermonuclear fus
ion researches. The paper describes the methodology employed to determ
ine the harmonic network impedance from current and voltage measuremen
t seen at the Camin-Padova node of the Italian transmission network, i
n which are injected the current harmonics produced by the reversed fi
eld pinch experiment (RFX) fusion facility; in particular, a simple me
thod for precise measurement of voltage harmonics is presented in deta
il.