S. Hanninen et M. Lehtonen, CHARACTERISTICS OF EARTH FAULTS IN ELECTRICAL DISTRIBUTION NETWORKS WITH HIGH IMPEDANCE EARTHING, Electric power systems research, 44(3), 1998, pp. 155-161
This paper presents an analysis and comparison of earth fault characte
ristics in the medium voltage distribution networks (20 kV) with high
impedance earthing. The results presented are based on the evaluation
of 476 real case data recordings, obtained from substations of distrib
ution networks with an unearthed or a compensated neutral during the o
bservation period of 3 years, 1994-1996. The networks were mainly of o
verhead construction, with a smaller share of underground cables. In t
he occurrence of disturbances, the traces of phase currents and voltag
es and neutral currents and voltages were recorded at two feeders at t
wo substations. The study dealt with the clearing of earth faults, rel
ation between short circuits and earth faults? are extinction, arcing
fault characteristics, appearance of transients and magnitudes of faul
t resistances. The results contribute to various developments of distr
ibution automation and protection systems. (C) 1998 Elsevier Science S
.A. All rights reserved.