S. Uchida et al., RELATION OF INSULATION RESISTANCE AND DETERIORATED RATIO OF REFERENCEVOLTAGE OF OIL-IMMERSED SURGE ARRESTER ELEMENTS ENCLOSED IN POLE TRANSFORMERS, IEEE transactions on power delivery, 13(2), 1998, pp. 453-458
About ten years have passed since oil immerse surge arrester elements
enclosed in 6.6kV Dole transformers been used. At, present. technical
developments are being demanded to judge the soundness of these oil im
mersed surge arrester elements by a simple method anti easily judge wh
ether these elements can he used or not on site. The authors empirical
ly investigated correlation between the insulation resistance and the
deteriorated ratio of the reference voltage of these oil-immersed surg
e arrester elements. It was found that the deterioration of the oil-im
mersed surge arrester elements can be detected by measuring the insula
tion resistance by a megger.