Sa. Mumma et Yp. Ke, FIELD TESTING OF ADVANCED VENTILATION CONTROLS FOR VARIABLE AIR VOLUME SYSTEMS, Environment international, 24(4), 1998, pp. 439-450
Results from the experimental phase of a larger research project are p
resented for three promising ventilation controls capable of meeting t
he ventilation requirements of ANSI/ASHRAE Standard 62-1989 (ASHRAE 19
89) with low energy use. Each control dynamically adjusted the outdoor
air (OA) requirement based upon occupancy and measured building zone
loads. Credit for unvitiated air from over-ventilated spaces was also
taken in each control. Controls 2 and 3 used primary airflow rate as a
n optimization variable to decrease the required OA flow rate, thus re
ducing the energy needed to condition OA. The supply air temperature i
n control 2 was a constant, but was an additional optimization variabl
e in control 3. The three ventilation controls were achieved by the si
mulation/optimization algorithms resident in a stand-alone personal co
mputer (PC) on site. A total of 24 days of performance data were colle
cted. Typical day data sets for each control are presented in some det
ail. The objective of the experimental phase was to verify the reliabi
lity of the simulation/optimization algorithms resident in the on-site
PC. That objective was met for each of the three controls since excel
lent agreement was found between the measured data and the control alg
orithm predictions. (C) 1998 Elsevier Science Ltd.