J. Suescun et al., DISSOLVED-OXYGEN CONTROL AND SIMULTANEOUS ESTIMATION OF OXYGEN-UPTAKERATE IN ACTIVATED-SLUDGE PLANTS, Water environment research, 70(3), 1998, pp. 316-322
The theoretical basis, practical implementation, and experimental vali
dation of an on-off control strategy for dissolved oxygen (DO) in aero
bic reactors of pilot-scale activated-sludge plants with simultaneous
estimation of oxygen uptake rate are presented. The effect of dead tim
e and a long response time for robust DO probes has been carefully ana
lyzed and corrected through modeling of the dynamic response of the se
nsor. Study results indicate that the amplitude of the control band de
pends on the dead time of the probe. Simultaneous estimation of the vo
lumetric mass-transfer coefficient for DO (K(L)a) permits a continuous
check of the aeration equipment. Experimental validation has been ach
ieved in a continuous pilot-scale plant.