ANALYSIS OF VERY FAST TRANSIENT OVERVOLTAGE IN TRANSFORMER WINDING

Citation
Y. Shibuya et al., ANALYSIS OF VERY FAST TRANSIENT OVERVOLTAGE IN TRANSFORMER WINDING, IEE proceedings. Generation, transmission and distribution, 144(5), 1997, pp. 461-468
Citations number
14
ISSN journal
13502360
Volume
144
Issue
5
Year of publication
1997
Pages
461 - 468
Database
ISI
SICI code
1350-2360(1997)144:5<461:AOVFTO>2.0.ZU;2-C
Abstract
Owing to the disconnector switch very fast transient overvoltages can generate a voltage oscillation inside the transformer connected to it. A practical method to analyse the oscillation is developed based on t he multiconductor transmission-line theory. The analysis is conducted in two steps in the frequency domain: first the whole transformer wind ing is simulated using a single transmission-line model, and secondly, the phenomena in the first coil are analysed using a multiconductor t ransmission-line model. The numerical results for an actual 525kV tran sformer conform with the experiment. The interturn voltage shows a res onance determined by the travelling waves in the coil. The propagation of travelling waves is visualised using time domain analysis.