An equivalencing procedure is presented to account for load areas under tap
-changing-under-load (TCUL) transformers in medium- to long-term dynamic st
udies, allowing reduction in dynamical order and number of nodes. Account i
s taken of specific models for interconnecting networks and loads, which ar
e supplied by TCUL transformers equipped with an automatic tap ratio regula
tor. The analysis leads to an equivalent TCUL transformer, feeding a consta
nt current load, which affects the rest of the system in the same way as th
e original transformers; this is acknowledged by comparing, both in steady-
state and dynamic conditions, voltage and current, and therefore active and
reactive power, at common specific buses in the original and equivalenced
system. Two test cases have been created, showing acceptable similarities b
etween the original system and the equivalenced system. Such promising outc
omes seem to ensure the opportunity to analyse large power systems, leading
to satisfactory results, for interesting quantities, without a loss of gen
erality and excessive time-consuming procedures.