The lifetime of resin insulated voltage transformers (RIVT) can be con
siderably shortened due to partial discharge activity taking place ins
ide the insulation close to the active parts of the component. In that
region the presence of voids, due to manufacturing processes, and the
enhanced electric field stress lead to an intense partial discharge a
ctivity which determines accelerated degradation processes and eventua
lly the ultimate failure of the device. Partial discharge measurements
together with an estimation of the electric field distribution in RIV
T seem to be indispensable in order to fully understand transformer pe
rformances. In this paper, a study of the electric field distribution
inside the RIVT, together with results of partial discharge tests are
presented. The influence of the various test arrangements and methods
on the experimental results are investigated.