PERFORMANCE AND HEAT-TRANSFER CHARACTERISTICS OF HFC-134A AND CFC-12 IN A WATER CHILLER

Citation
S. Devotta et al., PERFORMANCE AND HEAT-TRANSFER CHARACTERISTICS OF HFC-134A AND CFC-12 IN A WATER CHILLER, Applied thermal engineering, 18(7), 1998, pp. 569-578
Citations number
12
Categorie Soggetti
Engineering, Mechanical",Mechanics,Thermodynamics
Journal title
ISSN journal
13594311
Volume
18
Issue
7
Year of publication
1998
Pages
569 - 578
Database
ISI
SICI code
1359-4311(1998)18:7<569:PAHCOH>2.0.ZU;2-6
Abstract
A water chiller with an open reciprocating compressor has been used to comparatively assess the performance of HFC-134a with reference to CF C-12 under as close to identical conditions as possible. Performance c haracteristics of the chiller under retrofit conditions show that HFC- 134a offers better cooling load and coefficients of performance vis-a- vis CFC-12 for identical operating conditions. Further heat transfer a nalysis of data for the condenser shows that the condensing heat trans fer coefficients for HFC-134a are superior to CFC-12. The better perfo rmance of HFC-134a may be ascribed to the better heat transfer coeffic ient of HFC-134a over CFC-12. (C) 1998 Elsevier Science Ltd. All right s reserved.