STUDY ON AN AFTER-LAYING TEST FOR A LONG-DISTANCE GIL

Citation
T. Nojima et al., STUDY ON AN AFTER-LAYING TEST FOR A LONG-DISTANCE GIL, IEEE transactions on power delivery, 13(3), 1998, pp. 718-727
Citations number
20
Categorie Soggetti
Engineering, Eletrical & Electronic
ISSN journal
08858977
Volume
13
Issue
3
Year of publication
1998
Pages
718 - 727
Database
ISI
SICI code
0885-8977(1998)13:3<718:SOAATF>2.0.ZU;2-P
Abstract
Technologies for the after-laying test of a long-distance gas insulate d transmission line (GIL) have been developed for the detection oi par tial discharge (PD) and contact defects. We constructed long (168 m) t est line in a deep tunnel and clarified the propagation characteristic s of PD signals through the GIL as well as the spatial sensitivity and S/N characteristics of PD sensors for locating metallic particles, We have also proposed the application of a fiber-optic temperature distr ibution sensor for locating contact defects and confirmed the validity of this sensor for the GIL test line.