The dynamic safety system (DSS) is a computer based reactor protection
system that has dynamic self-testing feature and fail-safe nature inh
erently. The dynamic self-testing and fail-safe features provide a hig
h level of reliability and low spurious trip rate. The time and human
efforts maintaining the system can also be reduced by virtue of those
features. In order to apply the DSS for PWR, however, some modificatio
n is required because there exist many differences between PWR and AGR
for which the DSS was first tested and installed. These differences a
re trip algorithms, monitored parameters, trip logics, and other condi
tions. In this work, the DSS algorithm is modified for PWR. The modifi
ed DSS has several new features which are required for applying DSS te
chnology to PWR. Then, the modified DSS is implemented in a programmab
le logic controller (PLC) and tested. It is shown that, from the resul
ts, the modified DSS generates correct output in all test cases. (C) 1
998 Elsevier Science Ltd. All rights reserved.