RECENT RESEARCHES IN INDIRECT EVAPORATIVE COOLER - III - OPTIMIZATIONOF THE COOLING POTENTIAL OF A ROOM-COUPLED INDIRECT EVAPORATIVE COOLER

Citation
Tr. Tulsidasani et al., RECENT RESEARCHES IN INDIRECT EVAPORATIVE COOLER - III - OPTIMIZATIONOF THE COOLING POTENTIAL OF A ROOM-COUPLED INDIRECT EVAPORATIVE COOLER, International journal of energy research, 22(8), 1998, pp. 741-750
Citations number
10
Categorie Soggetti
Energy & Fuels","Nuclear Sciences & Tecnology
ISSN journal
0363907X
Volume
22
Issue
8
Year of publication
1998
Pages
741 - 750
Database
ISI
SICI code
0363-907X(1998)22:8<741:RRIIEC>2.0.ZU;2-3
Abstract
A mathematical model based on heat transfer principles, for characteri zing the cooling performance of a room coupled indirect evaporative co oler (tube type) has been developed. Two dimensionless parameters, i.e . environment factor, phi and cooling factor, CF have been defined to characterize the performance of IEC coupled with a room. The optimum v alues of these parameters have been obtained for different environment al and thermal load conditions. In addition to this, a linear relation ship has been obtained for the optimum size of a cooler to remove maxi mum heat from a room of given size. (C) 1998 John Wiley & Sons, Ltd.