HEAT-TRANSFER AUGMENTATION BY COILED WIRE INSERTS DURING FORCED-CONVECTION CONDENSATION OF R-22 INSIDE HORIZONTAL TUBES

Citation
Kn. Agrawal et al., HEAT-TRANSFER AUGMENTATION BY COILED WIRE INSERTS DURING FORCED-CONVECTION CONDENSATION OF R-22 INSIDE HORIZONTAL TUBES, International journal of multiphase flow, 24(4), 1998, pp. 635-650
Citations number
30
Categorie Soggetti
Mechanics
ISSN journal
03019322
Volume
24
Issue
4
Year of publication
1998
Pages
635 - 650
Database
ISI
SICI code
0301-9322(1998)24:4<635:HABCWI>2.0.ZU;2-#
Abstract
In the present work, heat transfer augmentation by coiled wire inserts during forced convection condensation of R-22 inside horizontal tubes has been studied. The test-condenser consisted of four separate coaxi al double pipe test sections assembled in series. It was a counterflow heat exchanger where R-22 condensed inside the inner tube by rejectin g heat to the coolant water flowing in the annulus. Coiled wires with three different wire diameters of 0.65, 1.0 and 1.5 mm and three diffe rent coil pitches of 6.5, 10.0 and 13 mm were made and used in full le ngth of test-condenser. The use of helically coiled wires were found t o increase the condensing heat transfer coefficients by as much as 100 % above the plain tube values on a nominal area basis. (C) 1998 Elsevi er Science Ltd. All rights reserved.