Rj. Galarza et al., AGGREGATION OF EXCITER MODELS FOR CONSTRUCTING POWER-SYSTEM DYNAMIC EQUIVALENTS, IEEE transactions on power systems, 13(3), 1998, pp. 782-788
Constructing a dynamic equivalent for a power system involves several
steps: the partition of the system involves several steps: the partiti
on of the system into coherent areas, the coherent area aggregation ex
citer models. A trajectory sensitivity method is used to tune the aggr
egate exciter parameters of the reduced models. The optimal results ar
e used to evaluate the aggregation from the DYNRED program and a weigh
ted the aggregation from the DYNRED program and a weighted MVA based m
ethod. A three-machine system with one coherent area satisfying the th
eoretical coherency conditions is used to investigate the impact of th
e variations of the individual generator, network, and excimer paramet
ers on the aggregate exciter model parameters. The results are then ap
plied to the exciter aggregation of a larger 48-machine system.