S. Grzybowski et Eb. Jenkins, AC AND LIGHTNING PERFORMANCE OF FIBERGLASS CROSSARMS AGED IN 115 KV TRANSMISSION-LINE, IEEE transactions on power delivery, 8(4), 1993, pp. 1914-1920
This paper presents the results of an investigation of the electrical
performance of 115 kV transmission line fiberglass crossarm used by Mi
ssissippi Power & Light Company. A transmission line fiberglass crossa
rm removed from service and companion crossarms stored outdoors but no
t in service were examined. The evaluation of electrical performance w
as based on flashover voltage value at AC voltage and standard lightni
ng impulse as well as under dry and wet conditions. The tests were per
formed in the Mississippi State University High Voltage Laboratory. Th
e obtained flashover voltages show no large difference in electrical s
trength of fiberglass crossarms removed from service and those stored
outdoors. The Added CFO voltage by fiberglass crossarm to the porcelai
n suspension insulators is presented versus the length of the fibergla
ss crossarm for dry and wet conditions.