VOLTAGE COLLAPSE AND CONTROL ACTIONS - EFFECTS AND LIMITATIONS

Citation
Acz. Desouza et Nhmn. Brito, VOLTAGE COLLAPSE AND CONTROL ACTIONS - EFFECTS AND LIMITATIONS, Electric machines and power systems, 26(9), 1998, pp. 903-915
Citations number
17
Categorie Soggetti
Engineering, Eletrical & Electronic
ISSN journal
0731356X
Volume
26
Issue
9
Year of publication
1998
Pages
903 - 915
Database
ISI
SICI code
0731-356X(1998)26:9<903:VCACA->2.0.ZU;2-I
Abstract
This paper focuses on control actions determination for voltage collap se prevention. Sensitivity matrices are proposed based on the knowledg e of the critical bus. By critical bus one means that bus whose state variables vary at most at the voltage collapse point. A tangent vector is used to identify the critical bus, and its behavior as a function of load increase is also investigated and compared with other indices previously proposed. It is shown that generator control actions may no t work to increase voltage collapse margin, whereas local control acti ons may produce better results. The tests are carried out in the IEEE- 300 bus test system, with and without reactive power limits considerat ion.