COMPARISON OF FAILURE RATES IN CONDUITS FOR UNDERGROUND HEAT DISTRIBUTION

Citation
C. Marsh et Jv. Carnahan, COMPARISON OF FAILURE RATES IN CONDUITS FOR UNDERGROUND HEAT DISTRIBUTION, Journal of transportation engineering, 124(6), 1998, pp. 589-593
Citations number
12
Categorie Soggetti
Engineering, Civil",Transportation
ISSN journal
0733947X
Volume
124
Issue
6
Year of publication
1998
Pages
589 - 593
Database
ISI
SICI code
0733-947X(1998)124:6<589:COFRIC>2.0.ZU;2-T
Abstract
A survey of existing underground heat distribution systems was conduct ed to compare the failure characteristics of steel conduits with fiber glass reinforced plastic conduits. Pressure testing was carried out in order to set an objective standard for performance. Plastic conduits were found to have a failure rate 4-5 times as high as steel conduits. The implications of this for a comparative life-cycle cost analysis a re very serious.