M. Abdulla et Z. Salameh, The effect of SVC's elements and power system's parameters on harmonic magnification: An experimental study, ELEC MACH P, 27(6), 1999, pp. 613-622
Static var compensator (SVC) is used to maintain constant load voltage by c
ompensating the var required by poor power factor loads. The SVC is also us
ed to balance the unbalanced three phase loads. The side effect of the SVC
is the generation of harmonic components. Under certain conditions, one of
the harmonic components generated by the SVC becomes magnified. This magnif
ied harmonic component leads to a time-bifurcation instability in the thyri
stor controlled reactors (TCR). This paper shows the effect of the SVCs ind
uctor on harmonic magnification and the time-bifurcation. The experimental
results are reported, and the time-bifurcation of the TCR current is genera
ted.