Effect of strip location on the air-side pressure drop and heat transfer in strip fin-and-tube heat exchanger

Authors
Citation
Hc. Kang et Mh. Kim, Effect of strip location on the air-side pressure drop and heat transfer in strip fin-and-tube heat exchanger, INT J REFR, 22(4), 1999, pp. 302-312
Citations number
17
Categorie Soggetti
Mechanical Engineering
Journal title
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID
ISSN journal
01407007 → ACNP
Volume
22
Issue
4
Year of publication
1999
Pages
302 - 312
Database
ISI
SICI code
0140-7007(199906)22:4<302:EOSLOT>2.0.ZU;2-D
Abstract
This work discusses about the pressure drop and heat transfer characteristi cs of a plain fin, a strip fin and combinations thereof in the fin-and-tube heat exchanger. Experimental apparatus and test algorithm using scale-up m odel fin geometry are discussed. The present work uses the electric heaters inside of the tube as the heating source to simulate the hot water loop in the wind tunnel test. The test results of the plain and strip fins are com pared with the existing correlation and experimental data. It was found tha t a hybrid fin, plain fin at front row and strip fin at rear row, was more effective to enhance the heat transfer than that of the whole strip fin at the same fan power. (C) 1999 Elsevier Science Ltd and IIR. All rights reser ved.