Hc. Kang et Mh. Kim, Effect of strip location on the air-side pressure drop and heat transfer in strip fin-and-tube heat exchanger, INT J REFR, 22(4), 1999, pp. 302-312
Citations number
17
Categorie Soggetti
Mechanical Engineering
Journal title
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID
This work discusses about the pressure drop and heat transfer characteristi
cs of a plain fin, a strip fin and combinations thereof in the fin-and-tube
heat exchanger. Experimental apparatus and test algorithm using scale-up m
odel fin geometry are discussed. The present work uses the electric heaters
inside of the tube as the heating source to simulate the hot water loop in
the wind tunnel test. The test results of the plain and strip fins are com
pared with the existing correlation and experimental data. It was found tha
t a hybrid fin, plain fin at front row and strip fin at rear row, was more
effective to enhance the heat transfer than that of the whole strip fin at
the same fan power. (C) 1999 Elsevier Science Ltd and IIR. All rights reser
ved.