Control of fouling in a spirally-ribbed water chilled tube with electronicanti-fouling technology

Authors
Citation
Yi. Cho et R. Liu, Control of fouling in a spirally-ribbed water chilled tube with electronicanti-fouling technology, INT J HEAT, 42(16), 1999, pp. 3037-3046
Citations number
16
Categorie Soggetti
Mechanical Engineering
Journal title
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER
ISSN journal
00179310 → ACNP
Volume
42
Issue
16
Year of publication
1999
Pages
3037 - 3046
Database
ISI
SICI code
0017-9310(199908)42:16<3037:COFIAS>2.0.ZU;2-M
Abstract
The objective of the present study was to investigate the feasibility of us ing electronic anti-fouling (EAF) technology to control precipitation fouli ng in a spirally-ribbed tube commonly used in chillers. Fouling experiments were conducted with two new tubes: one with an EAF treatment and the other without it. Brush punching of a fouled tube with an enhanced spin-grit bru sh cleaned almost all of the scale above the fins for the case with the EAF treatment, thus recovering 90% of the initial overall heat transfer coeffi cient values. However, for the case without the EAF treatment, the spin-gri t brush punching was not effective in removing scale. The present experimen t indicated that the EAF technology could be used to control precipitation fouling in a spirally-ribbed tube. (C) 1999 Elsevier Science Ltd. All right s reserved.