Improved application of power acceptability curves and their application to certain three-phase loads

Citation
Gt. Heydt et al., Improved application of power acceptability curves and their application to certain three-phase loads, ELEC MACH P, 27(7), 1999, pp. 737-751
Citations number
15
Categorie Soggetti
Eletrical & Eletronics Engineeing
Journal title
ELECTRIC MACHINES AND POWER SYSTEMS
ISSN journal
0731356X → ACNP
Volume
27
Issue
7
Year of publication
1999
Pages
737 - 751
Database
ISI
SICI code
0731-356X(199907)27:7<737:IAOPAC>2.0.ZU;2-M
Abstract
The electric power acceptability curves are loci in the bus voltage-disturb ance time plane. These loci separate regions of operation into "acceptable" and 'inacceptable." Several power acceptability curves exist, and this pap er discusses a constant energy model for the derivation of the curves. The application of the curves is discussed. The main foibles of the curves in t he undervoltage disturbance region are that they do not model three-phase e ffects and they were not designed for rotating loads. The paper proposes a solution to these drawbacks. The use of power acceptability curves for thre e-phase induction motors and six-pulse rectifier loads is discussed.