Cable crossings - Derating considerations part II - Example of derivation of derating curves

Citation
G. Anders et H. Brakelmann, Cable crossings - Derating considerations part II - Example of derivation of derating curves, IEEE POW D, 14(3), 1999, pp. 715-720
Citations number
3
Categorie Soggetti
Eletrical & Eletronics Engineeing
Journal title
IEEE TRANSACTIONS ON POWER DELIVERY
ISSN journal
08858977 → ACNP
Volume
14
Issue
3
Year of publication
1999
Pages
715 - 720
Database
ISI
SICI code
0885-8977(199907)14:3<715:CC-DCP>2.0.ZU;2-7
Abstract
Cables crossing other heat sources either perpendicularly or at oblique ang les will experience a rise in conductor temperature which should result in ampacity derating. In the first part of the paper a mathematical model for calculation of derating factors was presented, In this paper, a practical n umerical example is considered with a pipe-type cable crossing a 10 kV dist ribution circuit. The numerical analysis presented here confirms experiment al findings reported in the literature that the cable crossing may elevate are conductor temperature by as much as 20 degrees C.