Experimental validation of a thermal model for the ampacity derating of electric cables in wrapped trays

Citation
Rd. Figueiredo et al., Experimental validation of a thermal model for the ampacity derating of electric cables in wrapped trays, IEEE POW D, 14(3), 1999, pp. 735-742
Citations number
8
Categorie Soggetti
Eletrical & Eletronics Engineeing
Journal title
IEEE TRANSACTIONS ON POWER DELIVERY
ISSN journal
08858977 → ACNP
Volume
14
Issue
3
Year of publication
1999
Pages
735 - 742
Database
ISI
SICI code
0885-8977(199907)14:3<735:EVOATM>2.0.ZU;2-T
Abstract
As a safety measure for certain applications in Nuclear Power Stations, cab le trays must be wrapped with a fireproof material. In this paper a new imp lementation of a thermal model is presented, suitable for the determination of the ampacity derating of electric cables in wrapped trays. Model simula tion predictions have been compared with field tests to validate the model. Better agreement between simulations and experimental results is obtained when the standard procedure to determine the power loss in the cable mass i s modified to account for the actual measured height of the cable mass in t he tray.