Setting method of specific parameters of a superconducting fault current limiter considering the operation of power system protection - Resistance-type and rectifier-type SFCLs in overhead transmission systems

Citation
H. Kameda et H. Taniguchi, Setting method of specific parameters of a superconducting fault current limiter considering the operation of power system protection - Resistance-type and rectifier-type SFCLs in overhead transmission systems, IEEE APPL S, 9(2), 1999, pp. 1355-1360
Citations number
7
Categorie Soggetti
Apllied Physucs/Condensed Matter/Materiales Science
Journal title
IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY
ISSN journal
10518223 → ACNP
Volume
9
Issue
2
Year of publication
1999
Part
1
Pages
1355 - 1360
Database
ISI
SICI code
1051-8223(199906)9:2<1355:SMOSPO>2.0.ZU;2-L
Abstract
We have developed an EMTP model of a resistance-type and a rectifier-type f or super-conducting fault current limiter (SFCL) and defined their paramete rs which a user specifies when he plans to introduce an SFCL into a power s ystem. Using these models, we propose the setting method of these parameter s so as not to affect the response of protective relays when SFCLs operate.