EVALUATION OF LOAD SHEDDING TO PREVENT DYNAMIC VOLTAGE INSTABILITY BASED ON EXTENDED FUZZY-REASONING

Citation
Sk. Tso et al., EVALUATION OF LOAD SHEDDING TO PREVENT DYNAMIC VOLTAGE INSTABILITY BASED ON EXTENDED FUZZY-REASONING, IEE proceedings. Generation, transmission and distribution, 144(2), 1997, pp. 81-86
Citations number
13
Categorie Soggetti
Engineering, Eletrical & Electronic
ISSN journal
13502360
Volume
144
Issue
2
Year of publication
1997
Pages
81 - 86
Database
ISI
SICI code
1350-2360(1997)144:2<81:EOLSTP>2.0.ZU;2-N
Abstract
A reliable load-shedding approach, which makes use of a knowledge base and extended fuzzy reasoning, is proposed to arrest dynamic voltage i nsecurity following a disturbance. Irrespective of the nature of the d ynamic voltage instability, the location and required amount of load s hedding among load control buses can be promptly presented in realtime to the system operators. In the development of this scheme, fuzzy ind icators for all load control buses are firstly established and then co rrelated with the real load-shedding amounts decided during the off-li ne simulation study. The load-shedding amount for previously unseen op erating cases at each load control bus can be conservatively predicted according to the zone within which the fuzzy indicator falls.