The maximum potential energy savings from optimizing cold deck and hot deck reset schedules for dual duct VAV systems

Citation
Ms. Liu et De. Claridge, The maximum potential energy savings from optimizing cold deck and hot deck reset schedules for dual duct VAV systems, J SOL ENERG, 121(3), 1999, pp. 171-175
Citations number
5
Categorie Soggetti
Environmental Engineering & Energy
Journal title
JOURNAL OF SOLAR ENERGY ENGINEERING-TRANSACTIONS OF THE ASME
ISSN journal
01996231 → ACNP
Volume
121
Issue
3
Year of publication
1999
Pages
171 - 175
Database
ISI
SICI code
0199-6231(199908)121:3<171:TMPESF>2.0.ZU;2-K
Abstract
This paper presents the physical models for the maximum potential thermal e nergy savings from optimizing the hot deck and cold deck reset schedules fo r dual duct variable air volume systems. The maximum potential savings can be determined by using these models combined with basic system operating pa rameters and bin data. The system performance can be evaluated by comparing the actual savings with the maximum potential savings. The energy savings from optimal cold deck and hot deck reset schedules in multi-zone buildings should be at least 75 percent of the maximum potential savings.