The unit step response(USR) of lightning impulse voltage measuring systems
is numerically calculated with the help of the Numerical Electromagnetic Co
de (NEC-2), which calculates three-dimensional electromagnetic field around
conducting wires. The accuracy of this analysis is proved satisfactory thr
ough comparison of the results of measurement with calculation. The advanta
ge of this method is that the influence of the geometry: of the circuit can
automatically be calculated without evaluating stray capacitance in the sy
stem. Therefore. this method of analysis can be applied to the development
of an Impulse voltage divider, or in analyzing the influence of elements of
a USR measuring circuit. The influence of the shield ring attached to a re
sistance divider, and of the vertical metal sheet in the IEC-recommended US
R measuring circuit on the USR waveform is analyzed as examples.