Lg. Perez et Aj. Urdaneta, Optimal, coordination of directional overcurrent relays considering definite time backup relaying, IEEE POW D, 14(4), 1999, pp. 1276-1284
A methodology is presented for the consideration of definite-time backup re
lays in the optimal coordination of directional overcurrent relays using li
near programming. It is shown that the influence of considering second-zone
distance relays and breaker failure relays impose important requirements f
or the determination of the time dial settings of directional overcurrent r
elays. The paper introduces a revised formulation of the optimization probl
em. Results are presented for the application of the methodology on a power
system with 2 generators, 9 buses, 2 transformers and 7 transmission lines
.