Optimal, coordination of directional overcurrent relays considering definite time backup relaying

Citation
Lg. Perez et Aj. Urdaneta, Optimal, coordination of directional overcurrent relays considering definite time backup relaying, IEEE POW D, 14(4), 1999, pp. 1276-1284
Citations number
10
Categorie Soggetti
Eletrical & Eletronics Engineeing
Journal title
IEEE TRANSACTIONS ON POWER DELIVERY
ISSN journal
08858977 → ACNP
Volume
14
Issue
4
Year of publication
1999
Pages
1276 - 1284
Database
ISI
SICI code
0885-8977(199910)14:4<1276:OCODOR>2.0.ZU;2-Y
Abstract
A methodology is presented for the consideration of definite-time backup re lays in the optimal coordination of directional overcurrent relays using li near programming. It is shown that the influence of considering second-zone distance relays and breaker failure relays impose important requirements f or the determination of the time dial settings of directional overcurrent r elays. The paper introduces a revised formulation of the optimization probl em. Results are presented for the application of the methodology on a power system with 2 generators, 9 buses, 2 transformers and 7 transmission lines .