Aw. Kelley et al., Transformer derating for harmonic currents: A wide-band measurement approach for energized transformers, IEEE IND AP, 35(6), 1999, pp. 1450-1457
Power system transformers must often be derated when supplying harmonic cur
rents to nonlinear loads, IEEE Recommended Practice C57.110 extrapolates tr
ansformer loss for harmonic frequencies based on de winding resistance and
rated eddy-current loss, This paper describes an improved derating techniqu
e based on direct measurements performed at fundamental and harmonic freque
ncies. The measurements can be performed regardless of whether the transfor
mer is energized and in service or deenergized and out of service, For ener
gized transformers, the measurement can be performed regardless of whether
the transformer is fully loaded or unloaded. Measurements of several distri
bution transformers show the improvement of this method over C57.110.