Cy. Teo et Bg. He, Integrating three-phase load flow and short-circuit current calculation for a low voltage system, ELEC POW SY, 53(2), 2000, pp. 123-132
This paper summaries a dedicated approach to solve three-phase load flow an
d calculate unbalanced short-circuit current simultaneously for low voltage
systems without using the conventional symmetrical components. As the unba
lanced load and the neutral and shock voltages have to be modeled, the netw
ork equations including the representation of the neutral and grounding con
ductors are formulated entirely in phase coordinates. Test results demonstr
ate the ability in modeling the untransposed cable parameters and the influ
ence of the unbalanced load currents. More accurate results can thus be obt
ained as compared with other methods of calculation. Many interesting pheno
mena such as unbalanced load flow, different voltages appearing at various
sections of the neutral and grounding conductors, effects of the disconnect
ion of the source earthing, and any open-circuit fault can all be simulated
. (C) 2000 Elsevier Science S.A. All rights reserved.