An active power filter connected in series to the power distribution system
is presented and analysed, The series active power filter is implemented w
ith a three-phase PWM voltage-source inverter and operates with a resonant
LC passive filter connected in parallel to the power lines. The proposed sc
heme is able to simultaneously compensate current harmonics, the fundamenta
l negative and zero sequence voltage components generated by the voltage so
urce unbalance, and also eliminates the zero sequence current harmonic comp
onents that circulate through the neutral conductor. The active power filte
r is discussed in terms of the principles of operation under steady-state a
nd transient conditions. The design and implementation of the power and con
trol circuits are reported. Key predicted results are verified experimental
ly on a 5kVA prototype model.