Field experience with settings and coordination of the protective devices in a developed oil field plant

Citation
M. Gilany et al., Field experience with settings and coordination of the protective devices in a developed oil field plant, ELEC MACH P, 28(2), 2000, pp. 143-152
Citations number
8
Categorie Soggetti
Eletrical & Eletronics Engineeing
Journal title
ELECTRIC MACHINES AND POWER SYSTEMS
ISSN journal
0731356X → ACNP
Volume
28
Issue
2
Year of publication
2000
Pages
143 - 152
Database
ISI
SICI code
0731-356X(200002)28:2<143:FEWSAC>2.0.ZU;2-A
Abstract
This paper is concerned with updating the protective device settings and co ordination in an existing developed large industrial oil plant. Problems of short circuit carrying capacity of the system equipment, existence of diff erent protection systems, and outdoor dropout fuses, as well as guidelines for some protective devices, are considered. This paper gives in steps the proper procedure to deal with such problems in a developed industrial plant .